Aluminum SEU
| DOWNLOAD ALUMINUM SEU PDF |

| Applications | Top of Page |
May be used as service-entrance conductors when installed as required by NEC®
Article 230. May be used for branch circuits or feeders within a building as specified by
the NEC Section 338-10.
| Conductors | Top of Page |
Compact stranded AA-8000 Series aluminum alloy
| Conductor Insulation | Top of Page |
Type XHHW-2 conductors
Black XLP (cross-linked polyethylene), rated 90°C in wet or dry locations
Polarity ID: A red stripe on one conductor’s insulation surface
| Grounding Conductor | Top of Page |
Bare conductor strands are helically wound around two paralleled insulated conductors.
| Assembly | Top of Page |
Glass-reinforced tape applied over conductors
| Jacket | Top of Page |
Gray, sunlight-resistant PVC (polyvinyl chloride) over entire assembly
| Industry Standards | Top of Page |
UL Standard 44 (Insulated Conductors)
UL 854 Service Entrance Cables
Federal Specification A-A-59544
NFPA70: National Electrical Code®
| Surface Print | Top of Page |
Sample: AA-8000 AL TYPE SE CABLE STYLE U XHHW-2 660V 2 CDRS 2 AWG 1 CDR
4AWG (UL)
Product Code Number | 2 CONDUCTORS AWG | Concentric AWG | Approx O.D. Inches | Allowable Ampacities* | Approx. Net Wt. lbs./m ft. | UPC Code | |||
60°C ** | 75°C *** | 90°C **** | Dwelling ***** | ||||||
530-3600J | 6-6 | 6 | .458 x .720 | 40 | 50 | 60 | - | 143 | 662927580418 |
| 530-3600T | 6-6 | 6 | .458 x .720 | 40 | 50 | 60 | - | 143 | 048243580439 |
| 530-4600J | 2-2 | 4 | .559 x .919 | 75 | 90 | 100 | 100 | 259 | 662927580661 |
530-4800J | 2-2 | 2 | .559 x .919 | 75 | 90 | 100 | 100 | 282 | 662927580715 |
| 530-5200J | 1/0-1/0 | 1/0 | .680 x 1.125 | 100 | 120 | 135 | 135 | 428 | 662927580814 |
| 530-6000J | 2/0-2/0 | 2/0 | .736 x 1.221 | 115 | 135 | 150 | 150 | 514 | 662927580913 |
530-6600J | 4/0-4/0 | 2/0 | .818 x 1.406 | 150 | 180 | 205 | 200 | 692 | 662927581064 |
| 530-6800G | 4/0-4/0 | 4/0 | .857 x 1.445 | 150 | 180 | 205 | 200 | 762 | 662927581125 |
530-6800J | 4/0-4/0 | 4/0 | .857 x 1.445 | 150 | 180 | 205 | 200 | 762 | 662927581118 |
| * | Per Table 310-16 NEC® |
| ** | For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 through 1 conductors. |
| *** | For termination to equipment for circuits rated 100 amperes or marked for conductors larger than No. 1. |
| **** | Wet or dry locations. |
| ***** | For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load. |
Package Code | G | J | T |
AWG Size | 250' reel | 500' reel | 250' reel |
6-6-6 | X | X | |
2-2-2 | X | ||
| 2-2-4 | X | ||
| 1/0-1/0-1/0 | X | ||
| 2/0-2/0-2/0 | X | ||
| 4/0-4/0-2/0 | X | ||
| 4/0-4/0-4/0 | X | X | |