SER
| DOWNLOAD SER PDF |
.png)
| Applications | Top of Page |
May be used as service-entrance conductors and in other applications where SE cables are
permitted when installed as specified by NEC® Article 230. May be used in wet or dry locations
at temperatures up to 90°C.
| Conductors | Top of Page |
Stranded conductors: Uncoated copper per ASTM-B3, ASTM-B8, and ASTM-B787
| Phase Conductors | Top of Page |
Type THHN conductors
Black PVC (polyvinyl chloride), rated to 90°C in wet or dry locations
Jacketed with black nylon (polyamide)
One phase conductor has a red stripe on its insulation surface for easy polarity identification
| Neutral Conductor | Top of Page |
White PVC (polyvinyl chloride), rated 90°C
Jacketed with white nylon (polyamide)
| Equipment Ground Conductor | Top of Page |
Bare stranded copper conductor.
| Assembly | Top of Page |
Insulated and bare conductors are twisted together.
Glass-reinforced tape is applied over conductors.
| Jacket | Top of Page |
Gray, sunlight-resistant PVC (polyvinyl chloride) jacket over the complete assembly
| Industry Standards | Top of Page |
UL 83 (insulated conductors)
UL 854 Service Entrance Cables, File No. 11098
ASTM-B3
ASTM-B8
ASTM-B787
Federal Specification A-A-59544
NFPA70: National Electrical Code®
*It is the sole responsibility of the end user to determine suitability of this product for its intended end use and application.
| Surface Print | Top of Page |
Sample: TYPE SE CABLE STYLE R TYPE THHN OR THWN 3 CDRS 6 AWG 1 CDR 6 AWG
600V E11098-A (UL)
| Product Code Number | Size / Construction AWG | Stranding | Approx. O.D. Mils. | Allowable Ampacities* | Approx. Net Wt. Lbs./M Ft. | ||||
|---|---|---|---|---|---|---|---|---|---|
| Phase Conductor & Neutral | Equipment Grounding Conductor | 60°C ** | 75°C *** | 90°C **** | Dwelling ***** | ||||
| 136-3600J | 6-6-6-6 | 7 | 7 | 660 | 55 | 65 | 75 | -- | 411 |
| 136-4000J | 4-4-4-6 | 7 | 7 | 800 | 70 | 85 | 95 | 100 | 595 |
| 136-4400J | 3-3-3-5 | 7 | 7 | 905 | 85 | 100 | 110 | 110 | 738 |
| 136-4800J | 2-2-2-4 | 7 | 7 | 970 | 95 | 115 | 130 | 125 | 899 |
* Per Table 310.15 (B)(16) NEC®
** For termination to equipment for circuits rated 100 amperes or less, or marked for 14 AWG through 1 AWG conductors. See Art.
110.14 (C)(1) NEC®.
*** For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than No. 1 AWG.
See Art. 110.14 (C)(1) NEC®.
**** Dry or wet locations, for ampacity derating purposes.
***** For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3-wire, single-phase service conductors that
supply the total load. Per Table 310.15(B)(7) NEC®.
| Package Code | J |
|---|---|
| AWG Size | 500' Spool or Reel |
| 6-6-6-6 Stranded | X |
| 4-4-4-6 Stranded | X |
| 3-3-3-5 Stranded | X |
| 2-2-2-4 Stranded | X |