APPLICATIONS • For use in electrical distribution circuits not exceeding 600 volts phase to phase • Cables may be directly buried or installed in ducts • May be used in wet or dry locations at conductor temperatures not exceeding 90°C for normal operation, 130°C for emergency overloads and 250°C under short circuit conditions
CONDUCTORS • Hard drawn Class B stranded, compressed 1350 aluminum per ASTM B-231
CONDUCTOR INSULATION • Phase conductors: Black cross-linked polyethylene • Neutral conductor: Black crosslinked polyethylene with three continuous stripes of weather resistant yellow low density polyethylene extruded into the insulation 120° apart
ASSEMBLY • Phase conductors and neutral are twisted together with a left-hand lay not greater than 60 times the outside diameter of one phase conductor
INDUSTRY STANDARDS • ASTM B-230 • ASTM B-231 • ICEA S-105-692 • UL 854 Service Entrance Cables
SURFACE PRINT • Sample: 4/0 AWG AL XLPE USE-2 600V (UL)
|
|
Triplexed 600V Secondary UD Aluminum
|
|
Product Code Word/Number
|
Phase Conductors
|
Neutral
|
Cable O.D. Mils.
|
Approx. Net Wt.
lbs./ m. ft.
|
Ampacity for Direct Burial*
|
|
Size AWG
|
No. Strands
|
Ins. Thickness Mils.
|
Size AWG
|
No Strands
|
Ins. Thickness Mils.
|
|
Erskine 538-3600
|
6
|
7
|
60
|
6
|
7
|
60
|
642
|
133
|
100
|
|
Vassar 538-4000
|
4
|
7
|
60
|
4
|
7
|
60
|
742
|
191
|
130
|
|
Stephens 538-4800
|
2
|
7
|
60
|
4
|
7
|
60
|
830
|
248
|
168
|
|
Ramapo 538-5000
|
2
|
7
|
60
|
2
|
7
|
60
|
867
|
277
|
168
|
|
Sweetbriar 538-6800
|
4/0
|
19
|
80
|
2/0
|
19
|
80
|
1352
|
705
|
322
|
|
Monmouth 538-7000
|
4/0
|
19
|
80
|
4/0
|
19
|
80
|
1418
|
792
|
322
|
|
* Ampactites are based on 90°C conductor temperature, 20°C ambient RHO-90 earth, for cables buried 36” deep, only the phase conductors carrying current, 100% load factor. DO NOT USE THESE NUMBERS FOR NEC® APPLICATIONS!
|
|