PRODUCTS - COPPER SER

Type SE, Style SER
Service Entrance
THHN Copper Conductors/PVC Jacket
90°C Dry and Wet
600 Volts
Download PDF
 

APPLICATIONS
• May be used as service-entrance conductors and in other applications
  where SE cables are permitted when installed as specified by NEC®
  Article 230
• May be used in wet or dry locations at temperatures up to 90°C
CONDUCTORS
• Stranded conductors: Uncoated copper per ASTM-B3, ASTM-B8 and 
  ASTM-B787
PHASE CONDUCTORS
• Type THHN conductors
• Black PVC (polyvinyl chloride), rated 90°C dry or wet, jacketed with
  black nylon (polyamide)
• One of the phase conductors has a red stripe on the surface of the
  insulation for polarity identification
NEUTRAL CONDUCTOR
• White PVC (polyvinyl chloride), rated 90°C jacketed with white
  nylon (polyamide)
EQUIPMENT GROUND CONDUCTOR
• Bare stranded copper conductor
ASSEMBLY
• The insulated and bare conductors are twisted together
• A glass-reinforced tape is applied over the conductors
JACKET
• A gray, sunlight resistant PVC (polyvinyl chloride) jacket is applied over the
  complete assembly
INDUSTRY STANDARDS
• UL 83 (insulated conductors)
• UL 854 Service Entrance Cables, File No. 11098
• ASTM - B3
• ASTM - B8
• ASTM - B787
• Federal Specification A-A-59544
• NPFA70: National Electrical Code®
SURFACE PRINT
• Sample: TYPE SE CABLE STYLE R TYPE THHN OR THWN CDRS 3 CDRS 6
  AWG 1 CDR 6 AWG 600V E11098-A (UL)

 
Product Code
Size Construction AWG
Stranding
Approx. O.D. Mils.
Allowable Ampacities*
Approx. Net Wt. lbs./m ft.
Phase Conductor & Neutral
Equipment Grounding Conductor
60°C **
75°C ***
90°C ****
Dwelling *****
136-3600
6-6-6-6
7
7
660
55
65
75
-
411
136-4000
4-4-4-6
7
7
800
70
85
95
100
595
136-4400
3-3-3-5
7
7
905
85
100
110
110
738
136-4800
2-2-2-4
7
7
970
95
115
130
125
899
136-5200
1-1-1-3
19
7
1125
110
130
150
150
1140
136-6000
2/0-2/0-2/0-1
19
19
1250
145
175
195
200
1772
* Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for 14 AWG through 1 AWG conductors.  See Art. 110.14(C)(1) NEC®
*** For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than No. 1 AWG.  See Art. 110.14(C)(1) NEC®
**** Dry or wet locations - for ampacity deratng purposes.
***** For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load. Per Table 310-15(B)(6) NEC®.
Package Code
J
AWG Size
500' spool or reel
6-6-6-6 Stranded
X
4-4-4-6 Stranded
X
3-3-3-5 Stranded
X
2-2-2-4 Stranded
X
1-1-1-3 Stranded
X
2/0-2/0-2/0-1 Stranded
X