APPLICATIONS • 600 volt building wire for use in commercial and industrial applications as specified in the NEC® • 14 AWG - 2 AWG is marked VW-1 • 8 AWG - 2 AWG in black; Rated sunlight resistant
CONDUCTORS • Solid conductors: Uncoated copper per ASTM-B3 • Stranded conductors: Uncoated copper per ASTM-B3, ASTM-B787 (14 AWG - 4/0), and ASTM-B8 (250 MCM-750 MCM)
INSULATION • Color coded, heat and moisture resistant PVC (polyvinyl chloride)
JACKET • Nylon (polyamide), clear on 14 AWG - 2 AWG, black on 8-2 AWG
INDUSTRY STANDARDS • UL 83 - File No. E15119 • UL 1063 (MTW) - File No. E85964 • AWM - File No. E11829 • Canadian Standard C22.2 No. 75 and CSA Bulletin No. 1451 • ASTM: B3, B8, B787 • WC70/ICEA S-95-658 • Federal Specification A-A-59544 • NFPA70: National Electrical Code®
SURFACE PRINT • Sample: CERRO WIRE VINYLON-A 2 AWG (UL) MTW OR THWN-2 OR THHN OR GASOLINE AND OIL RESISTANT II OR AWM SUNLIGHT RESISTANT 600V-C(UL) TWN75 OR T90 NYLON
|
|
|
Product Code
|
Conductors
|
Covering
|
Approx. O.D. Inches
|
Allowable Ampacities*
|
Approx. Net Wt. lbs./m ft.
|
|
AWG Size
|
No. of Strands
|
PVC Ins. Mils.
|
Nylon jkt. Mils.
|
60°C **
|
75°C ***
|
90°C ****
|
|
112-14XX
|
14
|
SOL
|
15
|
4
|
0.104
|
15
|
15
|
15
|
15
|
|
112-16XX
|
12
|
SOL
|
15
|
4
|
0.120
|
20
|
20
|
20
|
23
|
|
112-18XX
|
10
|
SOL
|
20
|
4
|
0.151
|
30
|
30
|
30
|
37
|
|
112-34XX
|
14
|
19
|
15
|
4
|
0.110
|
15
|
15
|
15
|
16
|
|
112-36XX
|
12
|
19
|
15
|
4
|
0.130
|
20
|
20
|
20
|
24
|
|
112-38XX
|
10
|
19
|
20
|
4
|
0.165
|
30
|
30
|
30
|
39
|
|
112-40XX
|
8
|
19
|
30
|
5
|
0.217
|
40
|
50
|
55
|
63
|
|
112-42XX
|
6
|
19
|
30
|
5
|
0.253
|
55
|
65
|
75
|
96
|
|
112-44XX
|
4
|
19
|
40
|
6
|
0.322
|
70
|
85
|
95
|
153
|
|
112-45XX
|
3
|
19
|
40
|
6
|
0.350
|
85
|
100
|
110
|
190
|
|
112-46XX
|
2
|
19
|
40
|
6
|
0.380
|
95
|
115
|
130
|
233
|
|
| XX |
Color Add Code (See chart below) |
| * |
Per Table 310-16 NEC® |
| ** |
For termination to equipment for circuits rated 100 amperes or less, or marked for size 14 through 1 AWG conductors. Also for MTW used in wet locations or exposed to oil or coolant. |
| *** |
For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. Also for THWN-2 exposed to oil or coolant and MTW in dry locations. |
| **** |
For THHN used in dry locations and THWN-2 used in wet or dry locations. |
|
|