APPLICATIONS • For use in conduit as specified in the NEC® • For use as underground service entrance cable for direct burial per the NEC® • For use in wet or dry locations at temperatures up to 90°C
CONDUCTORS • Compact stranded, series 8000 aluminum alloy
INSULATION • Black XLP (cross-linked polyethylene)
INDUSTRY STANDARDS • UL 44 (RHH OR RHW-2) • UL 854 (USE-2) • Federal Specification A-A-59544 • NFPA70: National Electrical Code®
SURFACE PRINT • Sample: 2 AWG AA-8000 AL TYPE USE-2 OR RHH OR RHW-2600 V (UL)
|
|
|
Product Code Number
|
Conductors
|
Concentric AWG
|
Approx. O.D. Mils.
|
Allowable Ampacities*
|
Approx. Net Wt. lbs./m ft.
|
|
AWG Size
|
No. of Strands
|
60°C **
|
75°C ***
|
90°C ****
|
|
520-4200
|
6
|
7
|
60
|
0.299
|
40
|
50
|
60
|
44
|
|
520-4400
|
4
|
7
|
60
|
0.345
|
55
|
65
|
75
|
63
|
|
520-4600
|
2
|
7
|
60
|
0.403
|
75
|
90
|
100
|
92
|
|
520-5000
|
1/0
|
19
|
80
|
0.512
|
100
|
120
|
135
|
146
|
|
520-5200
|
2/0
|
19
|
80
|
0.555
|
115
|
135
|
150
|
177
|
|
520-5600
|
4/0
|
19
|
80
|
0.658
|
150
|
180
|
205
|
263
|
| * |
Per Table 310-16 NEC® |
| ** |
For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 through 1 conductors. |
| *** |
For termination to equipment for circuits rated 100 amperes or marked for conductors larger than No. 1. |
| **** |
Wet or dry locations. |
|
|