APPLICATIONS • For use in conduit or other recognized raceways for service, feeder, and branch circuit applications as specified in the NEC® • Good choice for industrial applications where better insulation toughness and resistance to moisture and heat is desired • For use in wet or dry locations at temperatures up to 90°C • Sunlight resistant
CONDUCTORS • Stranded conductors: Uncoated, soft copper per ASTM-B8 (2 AWG and 250 MCM - 750 MCM), and ASTM-B787 (1 AWG - 4/0)
INSULATION • XLP (cross-linked polyethylene)
INDUSTRY STANDARDS • UL 44 - File No. E63539 • CSA LL 82214 • ASTM-B3 • ASTM-B8 • ASTM-B787 • Federal Specification A-A-59544 • NFPA70: National Electrical Code® • NEMA WC70/ICEA S-95-658
SURFACE PRINT • Sample: 2 AWG XHHW-2 600V SUN-RES GASOLINE & OIL RESISTANT I & II (UL) E63539/XLPE RW90 (-40°C) CSA LL 82214
|
|
|
Product Code
|
Conductors
|
Insulation Thickness Mils.
|
Approx. O.D. Inches
|
Allowable Ampacities*
|
Approx. Net Wt. lbs./m ft.
|
|
AWG Size
|
No. of Strands
|
60°C **
|
75°C ***
|
90°C ****
|
|
117-4000
|
8
|
7
|
45
|
0.240
|
40
|
50
|
55
|
65
|
|
117-4200
|
6
|
7
|
45
|
0.280
|
55
|
65
|
75
|
97
|
|
117-4400
|
4
|
7
|
45
|
0.330
|
70
|
85
|
95
|
148
|
|
117-4500
|
3
|
7
|
45
|
0.353
|
-
|
-
|
110
|
180
|
|
117-4600
|
2
|
7
|
45
|
0.390
|
95
|
115
|
130
|
229
|
|
117-4700
|
1
|
19
|
55
|
0.450
|
110
|
130
|
150
|
293
|
|
117-5000
|
1/0
|
19
|
55
|
0.489
|
125
|
150
|
170
|
364
|
|
117-5200
|
2/0
|
19
|
55
|
0.530
|
145
|
175
|
195
|
449
|
|
117-5400
|
3/0
|
19
|
55
|
0.550
|
165
|
200
|
225
|
559
|
|
117-5600
|
4/0
|
19
|
55
|
0.640
|
195
|
230
|
260
|
698
|
|
117-6000
|
250
|
37
|
65
|
0.710
|
215
|
255
|
290
|
834
|
|
117-6400
|
300
|
37
|
65
|
0.760
|
-
|
-
|
320
|
995
|
|
117-6800
|
350
|
37
|
65
|
0.820
|
260
|
310
|
350
|
1152
|
|
117-7200
|
400
|
37
|
65
|
0.860
|
280
|
335
|
380
|
1309
|
|
117-8000
|
500
|
37
|
65
|
0.950
|
320
|
380
|
430
|
1622
|
|
117-8400
|
600
|
61
|
80
|
1.040
|
355
|
420
|
475
|
1947
|
| * |
Per Table 310-16 NEC® |
| ** |
For termination to equipment for circuits rated 100 amperes or less for size 14 through 1 AWG conductors. |
| *** |
For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
|
| **** |
Wet or dry locations. |
|
|