Max Print® is available for the following products: 1/0 AWG - 750 Kcmil THHN-2/THWN-2
|
|
Product Code
|
Conductors
|
Covering
|
Approx O.D. Inches
|
Allowable Ampacities*
|
Approx. Net Wt. lbs./m ft.
|
|
AWG/Kcmil Size
|
No. of Strands
|
PVC Ins. Mils.
|
Nylon jkt. Mils.
|
60°C **
|
75°C ***
|
90°C ****
|
|
112-50XX
|
1/0
|
19
|
50
|
7
|
0.480
|
125
|
150
|
170
|
373
|
|
112-52XX
|
2/0
|
19
|
50
|
7
|
0.524
|
145
|
175
|
195
|
460
|
|
112-54XX
|
3/0
|
19
|
50
|
7
|
0.575
|
165
|
200
|
225
|
573
|
|
112-56XX
|
4/0
|
19
|
50
|
7
|
0.630
|
195
|
230
|
260
|
714
|
|
112-60XX
|
250
|
37
|
60
|
8
|
0.700
|
215
|
255
|
290
|
850
|
|
112-64XX
|
300
|
37
|
60
|
8
|
0.750
|
240
|
285
|
320
|
1007
|
|
112-68XX
|
350
|
37
|
60
|
8
|
0.802
|
260
|
310
|
350
|
1173
|
|
112-72XX
|
400
|
37
|
60
|
8
|
0.847
|
280
|
335
|
380
|
1332
|
|
112-80XX
|
500
|
37
|
60
|
8
|
0.930
|
320
|
380
|
430
|
1648
|
|
112-84XX
|
600
|
61
|
70
|
9
|
1.030
|
355
|
420
|
475
|
1992
|
|
112-88XX
|
750
|
61
|
70
|
9
|
1.136
|
400
|
475
|
535
|
2462
|
| * |
Per Table 310-16 NEC® |
| ** |
For termination to equipment for circuits rated 100 amperes or less, or marked Nos. 14 through 1 conductors. Also for MTW used in wet locations or exposed to oil or coolant. |
| *** |
For termination to equipment for circuits rated over 100 amperes or marked for conductors larger then No. 1. Also for TWHN-2 exposed to oil or coolant and MTW in dry locations. |
| **** |
For THHN used in dry locations and THWN-2 used in wet or dry locations. |
|
|
|