Wire Size and Amp Ratings
| Copper | Aluminum | ||||
|---|---|---|---|---|---|
| 60°C (140°F) | 75°C (167°F) | 90°C (194°F) | 75°C (167°F) | 90°C (194°F) | |
| Wire Guage Size | NM-B, UF-B | THW, THWN, SE, USE, XHHW | THWN-2, THHN, | THW, THWN, | XHHW-2, THHN, THWN-2 |
14 | 15 | 15 | 15 | --- | --- |
12 | 20 | 20 | 20 | 15 | 15 |
10 | 30 | 30 | 30 | 25 | 25 |
8 | 40 | 50 | 55 | 40 | 45 |
6 | 55 | 65 | 75 | 50 | 60 |
4 | 70 | 85 | 95 | 65 | 75 |
3 | 85 | 100 | 110 | 75 | 85 |
2 | 95 | 115 | 130 | 90 | 100 |
1 | --- | 130 | 150 | 100 | 115 |
1/0 | --- | 150 | 170 | 120 | 135 |
2/0 | --- | 175 | 195 | 135 | 150 |
3/0 | --- | 200 | 225 | 155 | 175 |
4/0 | --- | 230 | 260 | 180 | 205 |
250 | --- | 255 | 290 | 205 | 230 |
300 | --- | 285 | 320 | 230 | 255 |
350 | --- | 310 | 350 | 250 | 280 |
500 | --- | 380 | 430 | 310 | 350 |
600 | --- | 420 | 475 | 340 | 385 |
750 | --- | 475 | 535 | 385 | 435 |
1000 | --- | 545 | 615 | 445 | 500 |
WARNING! Installation of electrical wire can be hazardous, if done improperly, can result in personal injury or property damage. For safe wiring practices, consult the National Electrical Code® and your local building inspector.