Aluminum USE-2

Aluminum USE-2              

DOWNLOAD ALUMINUM USE-2 PDF

 

Applications Top of Page


For use in conduit as specified by National Electrical Code®, or suitable for use as underground service entrance cable for direct burial per NEC®. For use in wet or dry locations at temperatures up to 90°C. 

Conductors Top of Page

 Compact stranded, Series 8000 aluminum alloy

Insulation Top of Page


Black XLP (cross-linked polyethylene) 

Industry Standards Top of Page

UL 44 (RHH or RHW-2)
UL 854 (USE-2)
ASTM-B3
Federal Specification A-A-59544
NFPA70: National Electrical Code®

Surface Print Top of Page


Sample: 2 AWG AA-8000 AL TYPE USE-2 OR RHH OR RHW-2600 V (UL)

 

 

         
Product Code NumberConductors
AWG
Size
Insulation Thickness (Mils)Approx. O.D.  Mils.Allowable Ampacities*Approx. Net Wt. Lbs./M Ft.UPC Code

60°C
**

75°C
***
90°C
****
         
 520-4200K6600.29040506044662927577012 
520-4400K4600.33555657563662927577418
520-4600K2600.390759010092662927577760
520-5000J1/0800.500100120135148662927578255
520-5000K1/0800.500100120135148662927578262
 520-5200K 2/0800.540115135 150179662927578316 
 520-5600J 4/0800.635150180 205265662927578408 
         

 * Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 through 1 conductors.
*** For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than No. 1.
**** Wet or dry locations.

 

   
Package CodeJK
AWG Size500' Reel
1,000' Reel 
   
6 Stranded X
4 Stranded X
2 Stranded X
1/0 StrandedXX
2/0 Stranded X
4/0 StrandedX